ardupilot/libraries/AP_BattMonitor/AP_BattMonitor_INA3221.h

Ignoring revisions in .git-blame-ignore-revs. Click here to bypass and see the normal blame view.

111 lines
3.8 KiB
C
Raw Permalink Normal View History

#pragma once
#include "AP_BattMonitor_config.h"
#if AP_BATTERY_INA3221_ENABLED
/*
*
* Datasheet: https://www.ti.com/lit/ds/symlink/ina3221.pdf?ts=1597369254046
*/
// The INA3221 takes two measurements for each channel: one for shunt voltage
// and one for bus voltage. Each measurement can be independently or
// sequentially measured, based on the mode setting (bits 2-0 in the
// Configuration register). When the INA3221 is in normal operating mode
// (that is, the MODE bits of the Configuration register are set to 111), the
// device continuously converts a shunt-voltage reading followed by a
// bus-voltage reading. This procedure converts one channel, and then continues
// to the shunt voltage reading of the next enabled channel, followed by the
// bus-voltage reading for that channel, and so on, until all enabled channels
// have been measured. The programmed Configuration register mode setting
// applies to all channels. Any channels that are not enabled are bypassed in
// the measurement sequence, regardless of mode setting.
// 8.3.3 Software Reset
// The INA3221 features a software reset that reinitializes the device and
// register settings to default power-up values without having to cycle power
// to the device. Use bit 15 (RST) of the Configuration register to perform a
// software reset. Setting RST reinitializes all registers and settings to the
// default power state with the exception of the power-valid output state. If a
// software reset is issued, the INA3221 holds the output of the PV pin until
// the power-valid detection sequence completes. The Power-Valid UpperLimit and
// Power-Valid Lowerlimit registers return to the default state when the
// software reset has been issued. Therefore, any reprogrammed limit registers
// are reset, resulting in the original power-valid thresholds validating the
// power-valid conditions. This architecture prevents interruption to circuitry
// connected to the powervalid output during a software reset event.
// The INA3221 has programmable conversion times for both the shunt- and
// bus-voltage measurements. The selectable conversion times for these
// measurements range from 140μs to 8.244ms.
#include "AP_BattMonitor.h"
#include "AP_BattMonitor_Backend.h"
#ifndef HAL_BATTMON_INA3221_MAX_DEVICES
#define HAL_BATTMON_INA3221_MAX_DEVICES 1
#endif
class AP_BattMonitor_INA3221 : public AP_BattMonitor_Backend
{
public:
/// Constructor
AP_BattMonitor_INA3221(AP_BattMonitor &mon,
AP_BattMonitor::BattMonitor_State &mon_state,
AP_BattMonitor_Params &params);
void init() override;
/// Read the battery voltage and current. Should be called at 10hz
void read() override;
bool has_current() const override {
return true;
}
static const struct AP_Param::GroupInfo var_info[];
private:
AP_Int8 i2c_bus;
AP_Int8 i2c_address;
AP_Int8 channel;
static struct AddressDriver {
bool read_register(uint8_t addr, uint16_t &ret);
bool write_register(uint8_t addr, uint16_t val);
bool write_config(void);
void timer(void);
void register_timer();
AP_HAL::OwnPtr<AP_HAL::I2CDevice> dev;
uint8_t bus;
uint8_t address;
uint8_t channel_mask;
uint8_t dev_channel_mask;
struct StateList {
struct StateList *next;
HAL_Semaphore sem;
uint8_t channel;
bool healthy;
float voltage;
float current_amps;
float delta_mah;
float delta_wh;
uint32_t last_time_micros;
};
StateList *statelist;
} address_driver[HAL_BATTMON_INA3221_MAX_DEVICES];
static uint8_t address_driver_count;
AddressDriver::StateList *address_driver_state;
};
#endif // AP_BATTERY_INA3221_ENABLED